Machine inertia
Machines

The Machine Inertia block models inertia and damping that you connect to the mechanical rotational R port of a three-phase machine. The block has an internal connection to a mechanical rotational reference. The figure shows an equivalent configuration to the Machine Inertia block using Simscape™ mechanical rotational components.

Based on the value you select for the Specify inertia
parameterization by parameter, you specify inertia J directly
or using the machine inertia constant H.
If you specify the inertia constant, the block calculates inertia by
J is inertia in kg⋅m2.
H is the inertia constant in sW/VA.
Srated is the machine rated apparent power in VA.
Frated is the machine rated electrical frequency in Hz.
N is the number of machine pole pairs.
You specify damping that represents viscous friction
between the machine rotor and mechanical rotational reference. Based
on the value you select for the Specify damper parameterization
by parameter, you specify a damping coefficient in SI units
or in per-unit. If you specify the damping coefficient in per-unit,
the block calculates the damping coefficient in SI units by
ωbase is the base mechanical speed in rad/s.
Tbase is the base damping torque in Nm.
Dbase is the base damping coefficient in Nm/(rad/s).
Dpu is the damping coefficient in per-unit.
D is the damping coefficient in SI units of Nm/(rad/s).
You can display machine parameters using the Power Systems menu on the block context menu.
Right-click the block and, from the Power Systems menu, select Display Parameters to display the machine per-unit base values and inertia parameters in the MATLAB® Command Window.
Machine rated apparent power. The default value is 555e6 V*A.
Nominal electrical frequency corresponding to the machine rated
apparent power. The default value is 60 Hz.
Number of machine pole pairs. The default value is 1.
Inertia specification. The default value is Inertia
constant, H.
Inertia constant. This parameter is visible only if you set Specify
inertia parameterization by to Inertia constant,
H. The default value is 3.525 sW/VA.
Inertia. This parameter is visible only if you set Specify
inertia parameterization by to Actual inertia,
J. The default value is 27548 kg⋅m2.
Damping specification. The default value is Per-unit
damping coefficient, pu_D.
Damping coefficient in per-unit. This parameter is visible only
if you set Specify damper parameterization by to Per-unit
damping coefficient, pu_D. The default value is 0.01.
Damping coefficient in SI units. This parameter is visible only
if you set Specify damper parameterization by to SI
damping coefficient, D. The default value is 39.0509 Nm/(rad/s).
Frequency initialization. The default value is Initial
electrical frequency.
Initial electrical frequency. This parameter is visible only
if you set Specify initialization by to Initial
electrical frequency. The default value is 60 Hz.
Initial mechanical frequency. This parameter is visible only
if you set Specify initialization by to Initial
mechanical frequency. The default value is 60 Hz.
The block has the following ports:
RMechanical rotational conserving port associated with the machine rotor
[1] Kundur, P. Power System Stability and Control. New York, NY: McGraw Hill, 1993.