Power (PLL-Driven, Positive-Sequence)
(To be removed) Compute positive-sequence active and reactive powers
The Specialized Power Systems library will be removed in R2026a. Use the Simscape™ Electrical™ blocks and functions instead. For more information on updating your models, see Upgrade Specialized Power System Models to use Simscape Electrical Blocks.
Library
Simscape / Electrical / Specialized Power Systems / Sensors and Measurements
Description
The Power (PLL-Driven, Positive-Sequence) block computes the positive-sequence active power P (in watts) and reactive power Q (in vars) of a periodic set of three-phase voltages and currents. To perform this computation, the block first computes the positive sequence of the input voltages and currents with a running window over one cycle of the fundamental frequency given by input 1. The reference frame required for the computation is given by the input 2. The first two inputs are normally connected to the outputs of a PLL block.
These formulas are then evaluated:
V1 is the positive-sequence component of input Vabc. I1 is the positive-sequence component of input Iabc.
With these formulas, a current flowing into an RL circuit produces a positive P and a positive Q.
As this block uses a running average window, one cycle of simulation must complete before the outputs give the correct value. For the first cycle of simulation, the output is held constant using the values specified by the Voltage initial input and Current initial input parameters.
Parameters
- Initial frequency (Hz)
Specify the frequency of the first cycle of simulation. Default is
60.- Minimum frequency (Hz)
Specify the minimum frequency value to determine the buffer size of the Variable Time Delay block used by the block to compute the phasors. Default is
45.- Voltage initial input [ Mag, Phase (degrees) ]
Specify the initial positive-sequence magnitude and phase (relative to the PLL phase), in degrees, of the voltage signals. Default is
[1, 0].- Current initial input [ Mag, Phase (degrees) ]
Specify the initial positive-sequence magnitude and phase (relative to the PLL phase), in degrees, of the current signals. Default is
[1, 0].- Sample time
Specify the sample time of the block, in seconds. Set to
0to implement a continuous block. Default is0.
Inputs and Outputs
FreqFundamental frequency (Hz) required by the computation. This input is normally connected to the output Freq of a PLL block.
wtAngle of the reference frame (rad/s) required for the computation. This input is normally connected to the output wt of a PLL block.
VabcThe vectorized signal of the three [a b c ] voltage sinusoidal signals. Typical input signals are voltages measured by the Three-Phase V-I Measurement block.
IabcThe vectorized signal of the three [a b c ] current sinusoidal signals. Typical input signals are currents measured by the Three-Phase V-I Measurement block.
PPositive-sequence active power (watts)
QPositive-sequence reactive power (vars)
Characteristics
| Sample Time | Specified in the Sample Time parameter Continuous if Sample Time = 0 |
| Scalar Expansion | No |
| Dimensionalized | No |
Version History
Introduced in R2013a