Weak Grid Model using Diesel Generator
Afficher commentaires plus anciens
Hi, I have a 100kW PV with 200kW load and I want to do the load frequency response with this steup for that I have to model a weak grid so that with the load change I can see the change in frequency and then use my frequncy controller to stabilise the frequency back to nominal avlue (50Hz). I am uncertain about the diesel generator modelling in Simulink. Currently, I have modelled it using Synchronous Machine with configuration as shown in the figure. Can you please tell me is this the correct way to model a weak grid using diesel genrator or not? Is there any better way to achieve this? I tried to do the load flow using powergui machine initialisation app to set the reference power for the SG during initialisation but it didn't worked so I have manually calcuated the value. In my case at initial conditions, the PV is providing 100kW and remaining 100kW should be provided by SM during initialisation so I have set the P_ref as 0.333.

1 commentaire
Abhipsa
le 12 Juin 2026 à 9:33
Using a Synchronous Machine with a governor is a reasonable approach for representing a diesel-generator-based weak grid. The weak-grid behavior will depend largely on the machine inertia and governor settings. Note that droop-based governor control alone will restore frequency to a new steady-state but with a persistent offset from 50 Hz. If your goal is full frequency restoration to exactly 50 Hz after a disturbance, you will need a secondary frequency controller (integral action) in addition to the governor droop.
Réponses (0)
Catégories
En savoir plus sur Power Converters dans Centre d'aide et File Exchange
Community Treasure Hunt
Find the treasures in MATLAB Central and discover how the community can help you!
Start Hunting!