Drive SampleClock to PFI signal as a sanity check.
1 vue (au cours des 30 derniers jours)
Afficher commentaires plus anciens
Hello! :)
I am doing some timing work and I would like to drive the internal sample clock on an NI USB-6259 board out to a PFI connection so I can sanity-check it using an oscilloscope.
I can find good MATLAB documentation on how to change the SampleClock to an external one, but I can't find out how to drive the internal SampleClock to an output.
How do you drive the internal SampleClock to a PFI output?
Thank you!
-Adam
0 commentaires
Réponses (1)
Manisha
le 24 Jan 2012
Hi Adam,
If you are uisng Session-based interface, you can use the R2012a prerelease and use the function
addClockConnection('Dev1/PFI1','external','ScanClock');
this would have the scan clock available at PFI1 of Dev1 for external use.
Hope that helps,
Manisha
0 commentaires
Voir également
Catégories
En savoir plus sur Simultaneous and Synchronized Operations dans Help Center et File Exchange
Community Treasure Hunt
Find the treasures in MATLAB Central and discover how the community can help you!
Start Hunting!