I cannot connect the blocks - three-phase current and voltage meter to the mains input
2 vues (au cours des 30 derniers jours)
Afficher commentaires plus anciens
Using the DC Fast Charger for Electric Vehicle, I would like to connect a three-phase current and voltage meter to the mains input, but I cannot connect the blocks. I intend to carry out this measurement at the input as I would like to check whether the input is impacted by connecting several chargers at the same time.
Please, help!

0 commentaires
Réponses (1)
Dallas Perkins
le 13 Oct 2023
Hi Jacques,
That block is from the Specialized Power Systems library which will not connect with Simscape Electrical connections. You will want to use this one instead:
0 commentaires