Output Fluctuation at Output of Multiple Connected Converters
5 vues (au cours des 30 derniers jours)
Afficher commentaires plus anciens
I am using the Simscape Electrical Specialized Power System to create a model of a grid-connected PV and battery system based on some schematic diagram provided to me. The problem is that the output current of the battery has very large fluctuations. Can anybody help me to troubleshoot this? Thank you!
0 commentaires
Réponses (1)
Joel Van Sickel
le 28 Mai 2024
The primary issue with your model is that the step size is too large. You have multiple PWM generators generating 10kHz switching signals. Since you are using a fixed step, you need to make your fixed step size at least 1/100 of your switching frequency. This means you need to set your powergui step size to 1 us and your simulink configuration step size to 1us. This will likely slow your model down by a factor of 50. Since it looks like you want to simulate for 100 seconds, this will be an incredibly slow simulation. I see that you are already using a VSC for the inverter. You should use the built in converters to make all of your power electronics average mode and remove all of the PWM generators so that you can have a faster simulation. You can always add the PWM back in later if you want a higher fidelity simulation.
Voir également
Catégories
En savoir plus sur Sources dans Help Center et File Exchange
Community Treasure Hunt
Find the treasures in MATLAB Central and discover how the community can help you!
Start Hunting!