Specification of the saturation characteristic for the model of the saturable transformer (Simulink Simscape Electrical - Specialized Power Systems)
5 vues (au cours des 30 derniers jours)
Afficher commentaires plus anciens
Hello everyone,
I am currently conducting research and I would like to use the Simulink model of the saturable transformer. According to the Matlab Help Center, when specifying the saturation characteristic, the magnetizing current is required.
I would like to clarify whether Matlab is referring to the current through the pure inductance L_sat (an inductive current) or if it includes the total current through the parallel branch of L_sat and R_m.
Thank you very much in advance for your assistance.
Best regards,
Torben
0 commentaires
Réponse acceptée
Vinay
le 1 Oct 2024
The "Saturable Transformer" utilizes the flux and magnetization current (`Im`) flowing through the inductor (`L_sat`) to assess the flux linkage. Additionally, it accounts for the excitation current (`IRm`) passing through the resistor(`Rm`) to incorporate the iron losses.
Kindly refer to the below documentation of “Saturable Transformer” for more details:
I hope this helps!
3 commentaires
Vinay
le 1 Oct 2024
Hi, The reactive current can indeed have a negative sign. This negative sign often appears because the inductive reactance is typically modeled with jωL, where L is the inductance. When modeling magnetization, the sign convention is based on the voltage-current relationship across the inductance. If the phase of the current lags the voltage by 90 degrees (as it does in inductive circuits), this can result in a reactive power that is conventionally negative, representing inductive behavior.
Plus de réponses (0)
Voir également
Catégories
En savoir plus sur Electrical Sensors dans Help Center et File Exchange
Community Treasure Hunt
Find the treasures in MATLAB Central and discover how the community can help you!
Start Hunting!