I have Positive sequence impedance and zero sequence impedance as well as 3 phase fault data os a substation source.
Z1 = 0.5 + j3.5 ohms Z0 = 0.4 + j3 ohms
I short circuit = 3961 Amps Voltage is 25 kV.
How can I model this in matlab simulink? Thank You.
Regards AC

Réponses (1)

Gautham Sholingar
Gautham Sholingar le 15 Mai 2017

0 votes

A good starting point to model this scenario is to look at the 'Three-Phase Mutual Inductance Z1-Z0' block which shows how to model 3-phase mutual inductance. The following documentation link explains this in detail:
The example link on this page: "power_3phmutseq10" illustrates the use of this block to build a three-phase inductive source with different values for the positive-sequence and zero sequence impedance.