Effacer les filtres
Effacer les filtres

Voltage measurement problem with isolated system ?

211 vues (au cours des 30 derniers jours)
Nicolo Blini
Nicolo Blini le 5 Juin 2018
Hi everyone.
I have some problems with this simulation. I try to explain: my load is an electric arc furnace and each "controlled voltage source" is the arc voltage. There is a non-grounded star point.
Externally, I have to measure the three phase-to-ground voltages of each arc for control system. (those three voltage measurement blocks) referred to ground.
When I start the simulation I have this problem:
"The Voltage Measurement block 'Voltage Measurement2' is connected between two isolated networks. For a valid measurement, the positive and negative terminals of the block must be connected to electrical nodes that are part of the same electrical circuit. Also check if the ground reference node is defined for that circuit."
I could solve the problem putting a grounded star point load, but it's not the reality. Furthermore, I can't change the secondary winding of MT/BT transformer to Yg because it is delta in reality.
Some ideas? What can I do ?
Thanks.
  3 commentaires
Muhd Haziq
Muhd Haziq le 3 Juil 2023
how to solve this ?
Luke McDevitt
Luke McDevitt le 10 Nov 2023
I still have this same problem

Connectez-vous pour commenter.

Réponses (2)

Saad Ullah Khan
Saad Ullah Khan le 16 Fév 2021
Add a large resistance in parallel for each phase.

Joel Van Sickel
Joel Van Sickel le 10 Juin 2024
You would never measure the voltage from a floating source to ground, so there is something wrong in your approach. You can either measure the line to line voltage, and convert it to phase voltage, or ground the system.

Community Treasure Hunt

Find the treasures in MATLAB Central and discover how the community can help you!

Start Hunting!

Translated by