OPC UA node browsing fails if server contains graphical items
Afficher commentaires plus anciens
I have been working through the Siemens Application Example “Virtual Commissioning with SIMATIC and Simulink” (link: https://support.industry.siemens.com/cs/ww/en/view/109749187 ) following the guides in documents “109749187_DIGI_Usecases_...” to use PLCSIM Advanced, OPC UA and Simulink as the test environment. Simulink however, is not able to see the contents of global data blocks in the PLC system. By using a third party OPC UA Client i have verified that the items are available from the PLC server. I have attached a report with more details, which was also sent to Siemens support. Their answer is quoted here:
" The problem lays in the implementation of the OPC UA Client within Matlab. As you already found out the browse is not working properly in the matlab client. The reason is the following: With FW2.5 we introduced the Node "icon" under each type (e.g.DataBlockGlobal) which represents a TIA icon (for visualization purpose in the clients). Since this change some clients need to adapt as they did not completely fullfil the OPC UA foundation spezifications. What happens is (simplified) the follwoing: If a Browse is executed on a type node like DataBlocksGlobal you will get the icon and a so called ContinuationPoint. If a ContinuationPoint is not null a BrowseNext has to be executed on this ContinuationPoint to get the additional nodes. This is not done in the OPC UA Client."
Is there any solution to this problem?
2 commentaires
Leonard Classen
le 20 Juin 2019
Modifié(e) : Leonard Classen
le 26 Juin 2019
Hello Jakob
I have exactly the same problem!
Did you come up with a solution for that?
Did you find an alternative solution? I do not need to use OPC UA. Currently I am looking into alternative methods to communicate between the PLC and Matlab, eg. TCPIP.
best regards
Leo
Jakob Rasmussen
le 20 Juin 2019
Réponse acceptée
Plus de réponses (1)
Felipe Ravazzi Iaconis
le 11 Juil 2019
2 votes
Hello,
Browsing of ContinuationPoints is not supported, but you can still access the variables directly:

So we do actually have a workaround for this. Just download the attachment and replace the file in the application example!
Best regards,
Felipe R.
4 commentaires
Jakob Rasmussen
le 22 Juil 2019
altay engtollykhar
le 5 Déc 2019
Hello Felipe,
I've tried your code to construct an OPC node in MatLab, but the node type is unknown, and when I try to retrieve the data it says 'Cannot call readValue on unknown node types.'
The OPC server is working fine, I can read and write through UaExpert.
-------------
code:
Var_Node_In = opcuanode(3,'''OpcInterface''.''fanForce''',uaClient);
result:

I don't know what went wrong.
Felipe Ravazzi Iaconis
le 5 Déc 2019
Hello,
What Matlab and OPC Toolbox versions are you using?
BR
Felipe
altay engtollykhar
le 5 Déc 2019
I'm using MatLab R2016b and OPC Toolbox Version 4.0.2(R2016b).
Catégories
En savoir plus sur Unified Architecture dans Centre d'aide et File Exchange
Community Treasure Hunt
Find the treasures in MATLAB Central and discover how the community can help you!
Start Hunting!