[Moist air chamber] Can the air inlet act as outlets?

3 vues (au cours des 30 derniers jours)
Diogo Martins
Diogo Martins le 7 Juil 2019
I'm trying to model a cooling tower, where you have 1 air inlet and one outlet. To do so I am using the constant volume chamber, which can have 2 inlets. However, the flowmeter at the exit (right side of the image) is not registering a value of zero and the pressure inside the tank rises, which leads me to believe that there is no outgoing flow.
Is there any way to make one of the inlets act as an outlet, or even a better way to model a cooling tower with the available simscape resources? I have also tried to use the moist air pipe model but to no avail.
Thanks in advance for any help

Réponses (1)

Erin McGarrity
Erin McGarrity le 4 Juin 2021
Hi Diogo,
You are correct, there is no flow. This is because the Pressure & Temperature Sensor (MA) is blocking the flow. This should be hooked to an Absolute Reference (MA) block as shown below to measure the output temperature from the chamber. I have attached an image of the correct model topolgy.
HTH,
Erin

Catégories

En savoir plus sur Simscape Fluids dans Help Center et File Exchange

Produits


Version

R2019a

Community Treasure Hunt

Find the treasures in MATLAB Central and discover how the community can help you!

Start Hunting!

Translated by